BLMPM - BATTERY WET FILLED WITH ACID CORROSIVE (SUP
- MSDS: BLMPM
- Manufacturer: EAST PENN MANUFACTURING CO INC
- Product Name: BATTERY WET FILLED WITH ACID CORROSIVE (SUP
- National Stock Number: 6850-00N021988
Product Identification
Product ID:BATTERY WET FILLED WITH ACID CORROSIVE (SUP
MSDS Date:11/09/1990
FSC:6850
NIIN:00N021988
MSDS Number: BLMPM
Responsible Party
LYON STATION, PA 19536
US
Emergency Phone: 215-682-6361
Info Phone: 215-682-6361
Cage: DO231
Contractor
Telephone: 610-682-6361
Cage: 04055
Ingredients
LEAD (SARA III)
CAS: 7439-92-1
RTECS: OF7525000
Fraction By Weight: 43-70%
OSHA PEL 0.05 MG/M3;1910.1025
ACGIH TLV: 0.15 MG/M3;DUST 9192
EPA Report Quantity: 1 LB
DOT Report Quantity: 1 LB
ANTIMONY (SARA III)
CAS: 7440-36-0
RTECS: CC4025000
Fraction By Weight: 0-4%
OSHA PEL 0.5 MG/M3
ACGIH TLV: 0.5 MG SB/M3; 9192
EPA Report Quantity: 5000 LBS
DOT Report Quantity: 5000 LBS
SULFURIC ACID (SARA III)
CAS: 7664-93-9
RTECS: WS5600000
Fraction By Weight: 20-44%
OSHA PEL 1 MG/M3
ACGIH TLV: 1 MG/M3; 9192
EPA Report Quantity: 1000 LBS
DOT Report Quantity: 1000 LBS
Hazards
LD50 LC50 Mixture:NONE SPECIFIED BY MANUFACTURER.
Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:NO IARC:NO OSHA:NO
Health Hazards Acute and Chronic:ACUTE: SULFURIC ACID MAY CAUSE
IRRITATION OF EYES, NOSE & THROAT. PROLONGED CONTACT MAY CAUSE
SEVERE BURNS. CHRONIC: REPEATED CONTACT CAUSES IRRITATION AND SKIN
BURNS. REPEATED EXPOSURE TO MIST MAY CA USE EROSION OF TEETH,
CHRONIC EYE IRRITATION AND/OR CHRONIC INFLAMMATION OF THE NOSE,
THROAT AND BRONCHIAL TUBES.
Explanation of Carcinogenicity:NOT RELEVANT
Effects of Overexposure:ACID CONTACT MAY CAUSE IRRITATION OF EYES, NOSE
& THROAT. BREATHING OF MIST MAY PRODUCE RESPIRATORY DIFFICULITY.
CONTACT WITH EYES AND SKIN CAUSES IRRITATION AND SKIN BURNS.
SULFURIC ACID IS A CORROSI VE CHEMICAL.
Medical Cond Aggravated by Exposure:PULMONARY EDEMA, BRONCHITIS,
EMPHYSEMA, DENTAL EROSION AND TRACHEOBRONCHITIS.
First Aid
First Aid:SKIN: FLUSH CONTACTED AREA W/LARGE AMOUNTS OF WATER FOR AT
LEAST 15 MINUTES. REMOVE CONTAMINATED CLOTHING & OBTAIN MEDICAL
ATTENTION. EYES: IMMEDIATELY FLUSH W/POTABLE WATER FOR A MINIMUM OF
15 MIN, S EEK ASSISTANCE FROM MD . INGEST: GIVE LARGE VOLUMES OF
WATER. DO NOT INDUCE VOMITING, OBTAIN MEDICAL TREATMENT. INHAL:
REMOVE TO FRESH AIR. SUPPORT BRTHG (GIVE O2/ARTF RESP) .
Fire Fighting
Flash Point:NON-FLAMMABLE
Lower Limits:4%
Upper Limits:74%
Extinguishing Media:CLASS ABC EXTINGUISHER, CO2 AND/OR HALON.
Fire Fighting Procedures:COOL EXTERIOR OF BATTERY IF EXPOSED TO FIRE TO
PVNT RUPTURE. ACID MIST/VAPS IN A FIRE SITUATION ARE CORR. WEAR
NIOSH/ MSHA APPRVD SCBA/FULL PROT EQUIP .
Unusual Fire/Explosion Hazard:HYDROGEN GAS, WHICH MAY EXPLODE IF
IGNITED, IS PRDCED BY THIS BATTERY, ESPECIALLY WHEN CHARGING. USE
ADEQ VENT/AVOID OPEN FLAMES/SPARKS/OTHER SOURCES OF IGNIT.
Accidental Release
Spill Release Procedures:SULFURIC ACID: DILUTE SPILL CAUTIOUSLY W/ FIVE
TO SIX VOLUMES OF WATER & GRADUALLY NEUTRALIZE W/SODIUM
BICARBONATE, SODA ASH OR LIME. WHEN EXPOSURE LEVEL IS NOT KNOWN,
WEAR NIOSH/MSHA APPROVED POSITIV E PRESSURE SCBA.
Neutralizing Agent:SEE SPILL/RELEASE PROCEDURES.
Handling
Handling and Storage Precautions:STORE AWAY FROM REACTIVE MATERIAL.
Other Precautions:SODIUM BICARBONATE, SODA ASH, SAND OR LIME SHOULD BE
KEPT IN SAME GENERAL AREA FOR EMERGENCY USE. IF BATTERY CASE IS
BROKEN, AVOID DIRECT CONTACT WITH INTERNAL COMPONENTS.
Exposure Controls
Respiratory Protection:NIOSH/MSHA APPROVED ACID GAS RESPIRATOR REQUIRED
WHEN PEL IS EXCEEDED OR EMPLOYEE WITNESSES RESPIRATORY IRRITATION.
Ventilation:WHEN CHARGING IN AN ENCLOSED AREA: LOCAL EXHST PREFERRED.
MECH(GEN) VENT ACCEPTABLE AT 1-4 AIR EXCHANGES/HR. (SUPP DATA)
Protective Gloves:ACID RESISTANT (EX: RUBBER) GLOVES.
Eye Protection:CHEM WORK GOG & FULL LENGTH FSHLD.
Other Protective Equipment:ACID-RESISTANT APRONS, BOOTS & PROTECTIVE
CLOTHING. EYEWASH & SHOWER STATIONS SHOULD BE MADE AVAILABLE.
Work Hygienic Practices:GOOD PERSONAL HYGIENE AND WORK PRACTICES ARE
MANDATORY.
Supplemental Safety and Health
MFR'S PART NO/TRADE NAME: MATERIAL, UN2794. VENT: LOCAL BUILDING/FIRE
CODES MAY REQUIRE EXPLOSION PROOF FANS & EQUIPMENT.
Chemical Properties
Boiling Pt:B.P. Text:235F,113C
Vapor Pres:13
Spec Gravity:1.220-1.325
Evaporation Rate & Reference:<1 (BUTYL ACETATE=1)
Solubility in Water:COMPLETELY
Appearance and Odor:CLEAR, ODORLESS, COLORLESS.
Stability
Stability Indicator/Materials to Avoid:YES
STRONG OXIDIZING AGENTS SUCH AS HOT NITRIC ACID, ETC.
Stability Condition to Avoid:CASES DECOMPOSE AT 160-410C (322-770F).
Hazardous Decomposition Products:COMBUSTION CAN PRODUCE CO2 AND CO.
Disposal
Waste Disposal Methods:LEAD-ACID BATTERIES ARE COMPLETELY RECYCLABLE.
DISPOSAL MUST BE IN ACCORDANCE WITH FEDERAL, STATE, AND LOCAL
REGULATIONS .
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.